Great BritainENControl panelHMI Gas 310/610 ECO PROInstallation, Userand ServiceManual125482-04

Seite 2 - Contents

4 Installation4.1 Control panel assemblyThe instrument panel HMI GAS 310/610 ECO PRO is standard fittedin the Gas 310/610 ECO PRO boiler.4. Installati

Seite 3

5 Commissioning5.1 Switch on the instrument panelFor operation of the boiler Gas 610 ECO PRO:The features and instructions described are for each boil

Seite 4

5.2 Reading out measured valuesFor operation of the boiler Gas 610 ECO PRO:The features and instructions described are for each boilermodule.5.2.1. Re

Seite 5 - 1 Introduction

5.2.2. Readout from the hour counter andpercentage of successful starts1. Press the two keys f simultaneously and then key [+] until thesymbol \ flash

Seite 6 - 1.3.3. User’s liability

State 5t Sub-status 5v3Burner for central heating operation30Temperature control31Limited temperature control (ΔT safety)32Output control33Increase pr

Seite 7 - 2 Safety instructions and

Parameter Description Adjustment rangeFactory settingGas 310 ECO PRO285 355 430 500 575 650p4Display screen0 = Simple1 = Comprehensive2 = Automatic sw

Seite 8 - 3 Technical description

Parameter Description Adjustment rangeFactory settingGas 310 ECO PRO285 355 430 500 575 650p33Gas valve leak provingsystem VPS(Accessory)0 = Not conne

Seite 9

nBoiler type Gas 610 ECO PROParameter Description Adjustment rangeFactory settingGas 610 ECO PRO570 710 860 1000 1150 1300p1Flow temperature: TSET20

Seite 10 - 4 Installation

Parameter Description Adjustment rangeFactory settingGas 610 ECO PRO570 710 860 1000 1150 1300p29Minimum gas pressurecheck Gps(Accessory)0 = Not conne

Seite 11 - 5 Commissioning

5.3.2. Modification of the user-level parametersParameters p1 to p5 can be changed by the user.CAUTIONModification of the factory settings may be detr

Seite 12 - 5. Commissioning

Contents1 Introduction ...41.1 Symbols used ...

Seite 13 - T000816-G

8. If necessary, set other parameters by selecting them using the[-] or [+] keys.9. Press the > key 2 times to return to the current operatingmode.

Seite 14 - Boiler type Gas 310 ECO PRO

5.3.5. Return to the factory settingsCAUTIONBy restoring the factory settings, customized settings canalso be erased. So first write down all the cust

Seite 15 - 160514 - 125482-04

5.3.7. Setting the manual modeIn some cases it may be necessary to switch the boiler to manualoperation, For example, if the controller has not yet be

Seite 16

6 Troubleshooting6.1 Shutdowns and lock-outsFor operation of the boiler Gas 610 ECO PRO:The features and instructions described are for each boilermod

Seite 17 - Boiler type Gas 610 ECO PRO

ShutdowncodeDescription Probable causes Checking / solution5v[4The maximum temperatureincrease speed tolerated inthe exchanger has beenexceeded4 Non-e

Seite 18

ShutdowncodeDescription Probable causes Checking / solution5v[22No flame during operation4 No ionization current4 Purge the gas supply to remove air4

Seite 19

ErrorcodeDescription Probable causes Checking / solutione[04e[054 Temperature of heatexchanger too low4 Exchangertemperature too high4 Bad connection4

Seite 20

ErrorcodeDescription Probable causes Checking / solutione[145 burner start-up failures4 No ignition4 Check cabling of ignition transformer4 Check the

Seite 21

ErrorcodeDescription Probable causes Checking / solutione[365x Flame loss4 No or insufficient ionizationcurrent4 Purge the gas supply to remove air4 C

Seite 22 - T005266-B

6.2.1. Error readout memorised1. Press the two keys f simultaneously and then key [+] until thesymbol c flashes on the menu bar.2. Select the installe

Seite 23 - T001632-B

6 Troubleshooting ...226.1 Shutdowns and lock-outs ...

Seite 24

6.2.2. Deletion of the error display1. Press the two keys f simultaneously and then key [+] until thesymbol c flashes on the menu bar.2. Select the in

Seite 26

Remeha Commercial UK - Part of the BDR THERMEARemeha HouseMolly Millars Lane WokinghamBerksRQ41 2QPAfter Sales Tel: 01189743076Technical Enquires: 011

Seite 27

3160514 - 125482-04

Seite 28 - 6.2 Error memory

1 Introduction1.1 Symbols usedIn these instructions, various danger levels are employed to draw theuser’s attention to particular information. In so d

Seite 29 - T001530-B

In the interest of customers, we are continuously endeavouring tomake improvements in product quality. All the specifications stated inthis document a

Seite 30 - T000831-D

2 Safety instructions andrecommendations2.1 Safety instructionsStrictly follow the safety instructions given.WARNING4 This equipment operates using el

Seite 31

3 Technical description3.1 Control panelFor operation of the boiler Gas 610 ECO PRO:Each module has its own instrument panel.3.1.1. Functions of the k

Seite 32 - © Copyright

3.1.2. Meaning of the symbols on the displayQInformation menu:Reading the various current values./On/Off switch (0/1):After 5 lock-outs, the boiler mu